Emergency lighting

Emergency built into the device
Wiring made with emergency lighting systems having the following characteristics:
230V-50/60Hz electronic inverter with battery over-discharge protection
Sealed Lithium Iron Phosphate (LiFePO4) or NiMH Battery
Status LED (Grid presence and battery charge indicator light)
Charging time 24 hours
Autonomy = 1 hour/3 hours (depending on the version ordered)
3-pole wiring for ordinary phase-to-ground-neutral (LTN) power supply
Additional 1-pole wiring for charging-emergency line supply (L not interruptible)
Compliance with EN 60598-1 and EN 60598-2-22 standards
Suitable for environments with temperature from 0°C to +25°C
Excluding high-risk areas

On request: wiring with intelligent centralized or local emergency lighting control and self-diagnostic systems - DALI

ENP Permanent Emergency

EP luminaires, in the presence of the mains voltage, illuminate like a normal luminaire-100% flux.

The LED module connected to the emergency kit, when the mains voltage fails, automatically turns on or stays on - reduced flux 3W/5W depending on the version ordered.

The luminous fluxes, stated in the data sheets, are the minimums guaranteed for the duration of the rated autonomy 1h/3h (depending on the version ordered), as required by the CEI EN 60598-2-22 standard and therefore are those to be considered at the design stage. The luminous fluxes indicated are intended to be REAL measured and in OUTPUT from the luminaire.

Non-permanent emergency ENP

In ENP luminaires, the LED module lights up only in emergency, when the mains voltage fails - reduced flux 3W/5W depending on the version ordered.

The luminous fluxes, stated in the data sheets, are the minimums guaranteed for the duration of the nominal autonomy 1h/3h (depending on the version ordered), as required by CEI EN 60598-2-22 and therefore are those to be considered at the design stage.

The luminous fluxes given are intended to be REAL measured and in OUTPUT from the luminaire.